SYMAP® Compact+
- GENSET Protection and Control (EC4)

 
 



Code Identifier. Code No. SHORT DESCRIPTION +EC4
1 +EC4

Application:
"GENSET Protection and control"
Standard equipment
Dimensions:
Housing dimensions (WxHxD): (210x250x87)mm
Dimensions front plate (WxHxD): (210x250x4)mm
Cutout (WxH): (192x232)mm
Front plate: "Stucke"-Logo (Design)
LED indication:
3 status-LEDs (Trip: red/Alarm: red-flashing/System: red/green)
8 LED indications (parametrizable, red/green)
Membrane keyboard:
6 x memebrane keys (menu navigation/parameter setting/Reset/password/ON/OFF)
Display:
Graphical LC-Display/Touchscreen (320x240 pixel)
Current measurement:
1 x CT1 (3-phase:0-25 x In); 1 x CT-GND1 (1-phase:measuring range optional)
Voltage measurement:
1 x PT1 (3-phasig: 50 – 130 V / 200 – 690 V);
1 x PT2 (3-phasig: 50 – 130 V / 200 – 690 V);
1 x PT3 (3-phasig: 50 – 130 V / 200 – 690 V);
1 x PT-GND1 (1-phasig: 50 – 130 V / 200 – 690 V)
Binary I/O:
Binary inputs: 19 pcs. (10 - 230V AC/DC; rooted)
Binary outputs: 12 pcs. (potential-free contacts)
Communication interfaces:
1 x mini-USB, on the side of the housing (parameter setting)
1 x CANBUS1/CANBUS2 (external communication)
1 x CANBUS 0 (Extended boards)
1 x RS422/RS485 (Modubus RTU; half- and full-duplex)
1 x USB interface (front plate; parameter setting)
Control and interlocking:
Control function: 5 switching devices;
Field interlocking: 8 switching devices
Gen-Set control functions:
Matching device (ANSI 15)
Powermanagement (Start/Stop)
Load sharing
Frquency controller
Power factor controller (cos phi)
Big concumer request (BCR)
Mains failure
Diesel control
Overspeed (ANSI 12)
Start phase
Stop phase (ANSI 5)
Preferential trip limits/Abnormal BUS condition
Additional limts
Protective functions:
ANSI: 24, 25, 25A, 27, 27Q, 27T, 32, 40, 46, 47, 49, 50, 50G, 50BF, 51, 51G, 51/46VR, 59G, 60L, 60FL, 67, 67G, 74TC, 78, 81, 81R 86, 95i, SOTF

S
       


Code Identifier. Code No. Secondary rated current CT1 +EC4
2 CT11 CT1: 1 A secondary, rated current (0-25×In) O
2 CT12 CT1: 5 A secondary, rated current (0-25×In) O
2 CT13 CT1-MP: 1 A secondary, rated current (0-25×In) O
2 CT14 CT1-MP: 5 A secondary, rated current (0-25×In) O
Code Identifier. Code No. Secondary rated current CT2 +EC4
3 CT10 without S
3 CT11 CT2: 1 A secondary, rated current (0-25×In), O
3 CT12 CT2: 5 A secondary, rated current (0-25×In), O
Code Identifier. Code No. Secondary rated current CT-GND1 +EC4
4 CTG1 CT-GND1: 1 A secondary, rated current (0-25×In) O
4 CTG2 CT-GND1: 5 A secondary, rated current (0-25×In) O
4 CTG3 CT-GND1: 1-20mA, secondary, rated current O
4 CTG4 CT-GND1: 20-100mA, secondary, rated current O
Code Identifier. Code No. Power supply - device +EC4
5 L 12-36 V DC O
5 M 36-72 V DC O
5 H 110-230 V AC; 110-300 V DC O
Code Identifier. Code No. Communication - Basic +EC4
16 KB0 without (Standard) O
16 KB1 Modbus RTU; RS422/RS485 (half- and full-duplex) O
Code Identifier. Code No. Communication - Interfaces +EC4
17 KS0 without (Standard) O
17 KS2 USB-A at front plate O
17 KS4 FO; Line diff. protection (2km; POF 2,5 (ST plug); Multimode 860 nm; diameter 65/125 um) O
17 KS5 FO; Line diff. protection (20km; POF 2,5 (ST plug); Monomode 1300 nm; diameter 9/125 um) O
7 KS6 RS422 (full-duplex, length of line: 300m); Line diff. protection O
Code Identifier. Code No. Communication - SCADA/Automation systems +EC4
18 KL0 without (Standard) S
18 KL1 Profibus DP ; RS485: D-SUB9 O
18 KL2 Profibus DP; FO O
18 KL3 IEC 60870-5-103; RS 485 O
18 KL4 IEC 60870-5-103; FO O
18 KL5 IEC 61850; RJ45 (Ethernet) O
18 KL6 IEC 61850; FO (star-topology) O
18 KL7 Modbus RTU; RJ45 (Ethernet) O
Code Identifier. Code No. Recorder unit +EC4
19 R0 without (Standard) S
19 R1 with recording unit O
Code Identifier. Code No. Additional protective function +EC4
20 P0 without (Standard) S
20 P2 ANSI 87: Current differential protection O
Code Identifier. Code No. Key switches +EC4
21 S0 1 x USB-Stick, coded (Standard) S
21 S1 1 key switch O
21 S2 2 key switch O
Code Identifier. Code No. Front plate (Design) +EC4
24 S "Stucke" (Standard) S
24 C Customer-specific model; on request (please indicate) O