SYMAP® - Technical Data
SYMAP® Y, X, BC
No. |
Description |
Condition / Characteristics |
1 |
Dimension (w x h x d): Y, X,
BC |
279 × 192 × 150 (mm);
279× 192× 110 (mm); 190 x 190 x 110 (mm)
|
2 |
Weight: Y, X, BC |
5 kg; 3.2 kg;
2.3 kg |
3 |
Power supply |
12-36 V DC, 36-72 V DC,
80-300 V DC or 60-230 V AC |
4 |
Power consumption |
<30 W |
5 |
Ambient
condition |
Service temperature |
-20°C to +70°C |
Storage temperature |
-40°C to +70°C |
Transport temperature |
-40°C to +70°C |
Humidity |
< 80 % |
6 |
Degree
of protection |
Front panel |
IP54 (IEC529) |
Terminals |
(IEC529) |
7 |
Vibration
|
Standards: |
IEC 60068-2-6 |
Frequency range: |
5 Hz to 100 Hz |
Cross-over frequency:
|
15,8 Hz; +/- 1,0 mm amplitude
to
1 g acceleration |
in 3 orthogonal axes (X,Y,Z)
|
8 |
Seismic
vibration |
Standards: |
KWU DWR 1300 |
Frequency range: |
5 Hz to 100 Hz |
Cross-over frequency: |
11,2 Hz; +/- 10,0 mm amplitude to
5 g acceleration |
Sweep rate 5 Hz to 35 Hz: |
1 Oct/min |
Sweep rate 35 Hz to 100 Hz: |
10 Oct/min |
in 3 orthogonal axes (X,Y,Z)
|
9 |
Tests
|
Electromagnetic compatibility |
EN 55011, EN 61000-4, KERI |
Protection functions |
IEC255, KERI |
|